Case studies · Failing connections
A broken jumper, 12 km out, fixed without an unplanned outage
The one customer it served noticed nothing. DFA reported each flare-up within about a minute, and meter pings led the crew to the pole.
- Where
- 25 kV circuit, United States
- DFA reported
- Series arcing, each flare-up within about a minute
- Circuit
- 25 kV, about 90 line-km
- Found
- A jumper broken at the surge arrester
- Outcome
- No unplanned outage

What DFA reported
A solid-copper jumper feeding a pole-top transformer broke where it attached to the surge arrester. Its stiffness kept it in contact, so it arced off and on, and the single customer it served reported nothing. DFA classified the flare-ups as series arcing and reported each one within about a minute.
What the crew found
Series arcing disrupts power-line-carrier meter traffic, so the utility pinged meters during a flare-up. Meters beyond the arcing answered off, which led the crew to the exact spot, about 12 electrical kilometers out on a circuit with about 90 line-km of conductor.
Why it matters
The utility replaced the jumper with only a short planned outage. DFA was its only notice.
Keep reading

A glowing substation switch, found within two hours
No calls, no SCADA alarm, normal meters. DFA reported series arcing, and a lineman found the failing switch before two days of storms.

Failing clamps, caught arcing and replaced
A failing clamp can arc for weeks before it burns through. Three finds show how DFA turns that warning into a work order.

31 days of warnings from one clamp, and what the first hunt taught
DFA tracked a failing clamp for a month on a 268-mile oilfield circuit. The co-op's first series-arcing search found it as it burned through.