What DFA reported
During a blind study, DFA detected one failing clamp 2,333 times over 21 days and summarized it as a single line on its report. For the first 19 days there was no conventional notice at all.
What the crew found
Then a group of customers had trouble four times in 40 hours: lights out, flickering, flickering, lights out. Crews answered each call the conventional way and struggled to find the root cause, replacing two pole-top transformers that were not faulty.
Why it matters
One clamp cost four trouble tickets, four truck rolls and two transformer replacements, mostly unnecessary and all on overtime, while a potential ignition source stayed on the line for three weeks.