Power Solutions DFA

Case studies · Recurrent faults

Two blinks a day apart led to a charred crossarm beside a pine forest

Nobody lost power for more than a blink. DFA matched the two faults, and the crew found a conductor burning into its crossarm six spans from the prediction.

Utility
Mid-South Synergy
DFA reported
Two matching faults about 24 hours apart
Circuit
Rural 25 kV, 109 miles of exposure
Found
Six spans from the predicted location
Outcome
Repaired in fair weather before any outage
1

What DFA reported

A broken insulator let a phase conductor drop onto its wooden crossarm. The first flashover tripped and reclosed a mid-point recloser. About 24 hours later a second fault did the same. Customers saw two blinks, and ordinarily nobody would have gone looking. DFA reported both faults from the substation.

2

What the crew found

The engineer who reviews DFA reports saw that the two faults matched in phase, current, duration and recloser response. He entered DFA's fault current into the circuit model and used the branch reclosers' records to choose between two candidate locations. A directed patrol found the displaced conductor and a heavily charred crossarm six spans from the prediction.

✓

Why it matters

The co-op made the repair in fair weather. Left alone, the arm or the conductor could have burned through: a sustained interruption, a pole-top fire, or a live conductor on the ground beside dry underbrush and pines.

Sources. CIGRE US National Committee Grid of the Future Symposium, Reston, 2018 (co-authored by Mid-South Synergy). 72nd Texas A&M Conference for Protective Relay Engineers, 2019.