Same fault twice in six days, and a dead squirrel found within hours

A breaker trip interrupted more than 1,200 customers twice. DFA linked the two faults within a minute, and the report took the crew to one pole.

Where
Overhead feeder, United States
DFA reported
Recurrent fault, within a minute of the second trip
Customers
More than 1,200 interrupted each time
Found
A dead squirrel on the phase A recloser
Outcome
Fixed within hours; no further faults
1

What DFA reported

A fault tripped the substation breaker and momentarily interrupted more than 1,200 customers. It began on phase A and pulled in phase B about ten cycles later. The breaker reclosed and, as usual, nobody acted. Six days later a near-identical fault tripped the breaker again. Within a minute DFA linked the two events and posted a recurrent-fault report.

2

What the crew found

The report's fault current, the way the fault spread from one phase to two, and extra trips of single-phase reclosers pointed the crew to one pole with single-phase reclosers. There they found a dead squirrel on the phase A recloser and damage on the phase B insulator, and fixed both within hours.

✓

Why it matters

No further faults followed. Each recurrence would have interrupted every customer on the circuit, and a carcass on a pole can draw birds and cause more faults for weeks.